Home / Switchgear technology / Current Transformers / Indoor Current Transformers / Support Current Transformers Type AK24, AK36
            
                    Indoor Current Transformers
Support Current Transformers Type AK24, AK36
- 24 – 36 kV Standard: IEC 60044-1/6
 - VDE 0414, ANSI, GOST
 
| Type: | AK24 | AK36 | 
|---|---|---|
| Operating voltage (maximum): | 24 kV | 36 kV | 
| Test Voltages: | 50/125 kV | 70/170 kV | 
| Rated frequency: | 50 or 60 Hz | 50 or 60 Hz | 
| Maximum rated primary current: | 1500 A | 1500 A | 
| Secondary rated current: | 1 or 5 A | 1 or 5 A | 
| Rated short-time thermal current lth (1s): | max. 60 (max. 1000 x lₙ) kA | max. 60 (max. 1000 x lₙ) kA | 
| Rated dynamic current l dyn: | max. 120 (2,5 x lth) | max. 120 (2,5 x lth) | 
| Weight: | approx. 20 kg | approx. 30 kg | 
                                Do you have special requirements?
We look forward to fulfilling your individual wishes. Contact us for customized solutions!
                        
Do you have questions about our product, would you like personal advice, or do you want to place an order? Our team is happy to assist you with help and guidance! Quality and expertise from a single source!
Operation Conditions for Current Transformers
- When the secondary terminals are connected to the measuring or protection devices, one of the terminals should be earthed for safety as seen in Figure CT-1.
 - The secondary circuit of a current transformer must not be operated with an open-circuit.
 - The secondary winding of a current transformer which will not be used must always be short-circuited and earthed as seen in Figure CT-2.
 - For the transformer with reconnectable and/or tapped secondaries, unused terminals must be left open as seen in Figure CT-3.
 - The current transformers which have capacitive divider tap (Ck) must be connected to the indicator. If the tap will not be used then it must be earthed as seen in Figure CT-4.
 
                Quality and expertise from a single source
For over 60 years, we have been successfully operating in the market as an owner-managed company. We combine tradition with innovation and stand for fairness and the highest quality. Founded more than six decades ago, we have continuously developed and established a recognized name.
Learn more about the company